DL/T5418-2009火电厂烟气脱硫吸收塔施工及验收规程(英文版)
上QQ阅读APP看本书,新人免费读10天
设备和账号都新为新人

7.3 Foundation Marking

7.3.1 Two mutually perpendicular center lines shall be marked on the absorber foundation based on the orientation as shown on the plan,with the deviation of the center point no greater than 10mm.

7.3.2 The equally dividing points on the foundation perimeter shall be clearly marked,including 0°,45°,90°,135°,180°,225°and 270°,with the foundation center as reference.

7.3.3 The center lines of the backing plates or sectional steel members beneath base plate of butt welds shall be marked,with the position deviation of the center lines no greater than 1.5mm.